arc ONLINE UPS | UON4
| Model | UON4 | 
| Capacity | 10000VA/9000W | 
| Input | Rated voltage: 220VAC | 
| Output | Voltage: 220VAC±2% | 
| Battery | Batteries voltage: 192VDC | 
| Dimension (W*H*D)(mm) | 212*500*420 | 
arc ONLINE UPS | UON4
| Model | UON4 | 
							  
| Capacity | 10000VA/9000W | 
							  
| Input | 
                                  Input system: Single phase & earth ground  Rated voltage: 220VAC Voltage range: 176-276VAC Frequency: 40-70Hz Power factor: 0.98 Voltage range of bypass: 80VAC×(1±5%)~285VAC×(1±5%)  | 
							  
| Output | 
                                  Output system: Single phase & earth ground Voltage: 220VAC±2% Power factor: >0.98 Output frequency: AC mode: 1.The output frequency is the same as the input frequency when the input frequency is in the range of 46 -54 Hz 2.The output frequency is 50Hz when the input frequency is not in the range of 46 -54 Hz Output frequency: DC mode: 50±0.2 Hz Transfer time: 0ms(AC→DC), <4ms(DC→Bypass) Crest factor of load: 3:1  | 
							  
| Battery | 
                                  Batteries voltage: 192VDC  Battery capacity*Quantity: 12VDC×16 Backup Time(25℃): Battery Capacity Charge time: Charger to 90% battery capacity in 4 hours(Standard), Dependent on the capacity of external batteries(long backup time)  | 
							  
| Environment | 
                                  Ambient temperature: 0-40℃  Environment humidity: 20-90%(no condensation) Altitude: Lower than 1000 m , Over 1000m: 1% de-rating for every 100 m rise Storage temperature: -25-55℃  | 
							  
| EMC | 
                                  ESD: IEC61000-4-2 LEVEL4  RS: IEC61000-4-3 LEVEL3 EFT: IEC61000-4-4 LEVEL4 Surge: IEC61000-4-5 LEVEL4  | 
							  
| Dimension (W*H*D)(mm) | 212*500*420 | 
							  
| Weight (standard/long backup time) (Kg) | 15.9 | 
| Safety | CE,IEC62040-1 | 
| Industry | ISO, RoHS | 
| Warranty | 12 months |