• Instrumentation cable Instrumentation cable Instrumentation cable
    Instrumentation cable

INSTRUMENTATION CABLE

DESCRIPTION

These cables are generally used for indoor/outdoor installation and suitable for wet and damp areas. Generally used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments.

STANDARD

BS 5308-1, 2 and Type- 1, 2

VOLTAGE GRADE

U/U : 300/500 V

CONSTRUCTION

1.      Conductor: Solid/ Flexible/ Stranded Circular, Plain annealed Copper or Tinned Copper, Class 1 or Class-2 or Class 5 to BS     6360

2.      Insulation: PVC-TI1 to BS 7655 or Polyethylene (PE) to BS 6234

3.      Pairing: Two insulated core uniformly twisted together

4.      Individual screen: Aluminium/polyester tape is applied over the laid up pairs with copper or tinned copper drain wire

5.      Binder: PETP tape

6.      Collective screen: Aluminium/polyester tape is applied over the laid up pairs with tinned copper drain wire

7.      Bedding: Polyethylene (PE) to BS 6234 or PVC, TM-1 to BS 7655

8.      Armour: Round Galvanized Steel wire

9.      Sheath: PVC-FR, TM-1-FR to BS 7655

 

COLOUR

Insulated core :         As per standard or other colors on request

Sheath :                    (Black or Blue or Other Colors available on request)


 Instrument (OS):

 Instrument (IS-OS):


 Instrument Armoured (OS):

 Instrument Armoured (IS-OS):


  • Low susceptibility to interference
  • Extremely cost-effective.
  • Low signal loss
  • First and efficient signal transmissions
  • Long operating life.